Powerwalker VI 400 SE User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 220
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
9. Specifications
Model VI 400 SE VI 600 SE VI 800 SE
CAPACITY 400VA / 240W 600VA / 360W 800VA / 480W
INPUT
Voltage 220~240 VAC
Voltage Range 170~280 VAC
Frequency Range 50/60Hz±1Hz
OUTPUT
Voltage Regulation +/-10%
Transfer Time Typical 2-6ms, 10ms max.
Waveform Modified Sine Wave
Protection Short circuit and overload protection
BATTERY
Type & Number 12V / 4.5Ah x 1 12V/ 7Ah x 1 12V/ 9Ah x 1
Charging Time 6 hours recover to 90% capacity
Protection Discharge and overcharge protection
Backup Time (est. 120W) 8 min 16 min 20 min
PHYSICAL
LED Indicator Green LED (AC Mode, Backup Mode)
Dimension (DxWxH) 333mm x 111mm x 143mm
ENVIRONMENT
Humidity 0-90 % RH @ -10° to 40° C (non-condensing)
Noise Level Less than 40dB
Model
VI 1000
SE
VI 14
00
SE
VI 2000
SE
CAPACITY
1000
VA / 600W
14
00VA /
840
W
2000VA / 120
0
W
INPUT
Voltage
220/230/240 VAC
Voltage Range
162~290 VAC
Frequency Range
50/60 Hz (Auto sensing)
OUTPUT
Voltage Regulation
+/
-
10%
Frequency Range
50 or 60 Hz +/
-
1 Hz
Transfer Time
Typical 4
-
8
ms, 10ms max.
Waveform
Stepped
Sine Wave
BATTERY
T
ype & Number
12V
/
7Ah
x 2
12V / 9Ah
x 2
12V / 9Ah
x 2
Charging Time
10h
to 90% capacity
6h
to 90% capacity
6h
to 90% capacity
Protection
Overload, discharge and overcharge protection
Backup Time
(est. 240W)
11 min
18 min
20 min
PHYSICAL
LCD Indic
ator
Input/output voltage, AC mode, Load level, Battery capacity
Dimension (DxWxH)
230mm
x
452mm
x
292
mm
ENVIRONMENT
Humidity
0
-
90 % RH @ 0
-
40° C (non
-
condensing)
N
oise Level
Less than 45
dB
EN
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 219 220