Diagram515
Step2 Selectremoteshutdownconditions.
Step3 Add/DeleteremotesystemIPaddress.
Step4 Click“Apply”buttontosavealldata.
NOTE:Click“Default”buttontorecoverthedefaultsetting.
Conditions:
l WhentheUPSisrunningfrombattery,shutdowntheremotesystemsafterxx
minxxsec:Whenclickingthecheckbox,remotesystemswhicharepoweredby
monitoredUPSwillshutdownaftermonitoredUPSrunningonbatterymodefor
xx min xx sec. The maximum setting number for minutes is 999, and for
secondsis59.
l Remoteshutdownwhenthecapacityofbatterydowntoxx%(Batterymode):
Whenclickingthischeckbox,localUPSwillstilloperateuntilthebatterycapacity
isdowntoxx%.Untilthen,itwillremotelyshutdownPCs.
l Immediately shut down the following remote systems when the battery is
runninglow:Whenclickingthecheckbox,remotesystemswhicharepowered
bymonitoredUPSwillshutdownwhenmonitoredUPSisatlowbatterylevel.