NetAgent UPS SNMP Agent User’s Manual
4 Section3. NetAgent Models 3.1 NetAgent Models NetAgent II Model P/N Package Contents Internal/External 1/3 Ports 1/3 phasesCP504 CT504 1. 1Port
5 DP532 DT532 1.Enternal NetAgent Mini with LCD Display 2. NetAgent Utility CD 3. User Manual 4. 5.3V DC adapter External *DT/CT version same dimensio
3.2 Pictures of NetAgent II NetAgent II(BP,CP/CT,DP/CT Series) CP504 CP503 BP506 BP505 NetAgent Mini (DP Series) DP520 DP522 DP532 6 DP
3.3 NetAgent Package Contents n NetAgent Utility CD, including: ♦ Netility:Configure NetAgent IP address, update firmware ♦ ClientMate:Windows, Linux,
3 Ports NetAgent (Internal / External) : LED Table Yellow Red Green Status Solid Off Solid Off Solid ON Power ON Flashing Solid ON Soli
3.5 NetAgent Mini Out looking NetAgent Mini External NetAgent Mini Internal Module Light signal application of NetAgent Mini - Status
Chapter 2. NetAgent UPS Installation Before using the NetAgent, the proper hardware and software configuration is necessary. Hardware installation
Chapter 3. NetAgent, UPS and Network Connection NetAgent II and NetAgent Mini provides External and Internal model for different UPS interface requir
Section2. Install the NetAgent Mini with UPS and Network NetAgent Mini - External NetAgent Mini -Internal oTo UPS nTo LANpTo DC Adapter nTo LA
Chapter 4. Using Netility Setup IP.Update Firmware Section1. Install Netility n Insert NetAgent Utility CD to the CD-ROM driver and execute Netili
User Guide for NetAgent Version 6.0 Firmware version 2.42 Copyright Information Copyright © 2000-2009, Mega System Technologies, Inc. All rights rese
n Launch Device Click Launch Device or double click the NetAgent listed in the table to launch it. Enter the Account (Login Name) and Password (Login
For example, ) Set 81 as HTTP port number, then http://192.168.0.177:81 must be typed at the web address to proceed to Netagent UPS’s website. ) S
p Firmware Upgrade NetAgent offer convenient firmware upgrade function. When you are going to upgrade firmware, click Download Firmware from NetAge
Chapter 5. UPS Web management by NetAgent Section1. Introduction After finishing NetAgent installation, including hardware installation and IP setting
Section2. NetAgent UPS Web Interface Enter NetAgent UPS Web page,there are 4 main function items in the first Web page: 2.1 Information 2.2 Configura
2.1 Information Sub-Menu : 2.1.1 System Status 2.1.2 Basic Information 2.1.3 Current Status 2.1.4 Remote Control 2.1.5 Meter/Chart 2.1.6 Modem Statu
2.1.1 System Status This page is to show NetAgent system information and Network settings. Values shown here are either provided by NetAgent itself or
2.1.2 Basic Information This page is to show UPS basic information. Values here are either provided by the UPS or they are user settings from the Conf
2.1.3 Current Status This page is to show the UPS current status. Users can choose an interval from the drop-down box to refresh the status readings.
10 Second Test This to perform 10 seconds UPS self test Deep Battery Test This function is to execute XX minute deep battery test Test Until Battery
Contents Chapter1. Introduction ________________________________________ 1 Section1. Features __________________________________________ 1 Section2. A
2.1.5 Meter/Chart This page displays temperature, capacity, load, voltage..etc of the UPS by appearing with meters/chart diagram. Fig.20 Meter/Chart
2.1.6 Modem Status (For 3 Ports NetAgent II only) This page displays Modem’s status and information. when 3 ports NetAgent II connects with modem. M
2.1.7 Environment Sensors-NetFeeler II 3 Ports NetAgent could be connected to NetFeeler II to detect the environmental status. NetFeeler II is to dete
2.2 Configuration Sub-Menu : 2.2.1 UPS Configuration 2.2.2 UPS On/Off Schedule 2.2.3 Network 2.2.4 SNMP 2.2.5 Email 2.2.6 SMS 2.2.7 Modem 2.2.8 WEB
2.2.1 UPS Configuration This page is to set the UPS configuration. Any wrong settings will cause incorrect display values or disconnection between the
Critical Capacity (%) This section is to set the UPS critical battery capacity (shown as % )NetAgent will send warning messages when UPS low battery o
2.2.2 UPS On/Off Schedule This page is to schedule On/Off time for the UPS and Wake On Lan. Weekly Schedule This section is to set the time to tur
2.2.3 Network This page is to set NetAgent Network settings. IP Address IP Address This section is to set NetAgent IP address. Subnet Mask Thi
Domain Name This is the Domain Name you have created from the above selected DDNS provider. Login Name This is the Login / Account name that you have
Fig.25 Network 33
2.1.3 Current Status______________________________________ 22 2.1.4 Remote Control ____________________________________ 22 2.1.5 Meter/Chart__________
2.2.4 SNMP This page is to set NetAgent SNMP settings so it can be used by a NMS ( Network Management System). (Eg: SNMPView, SNMPView can be fou
Fig.26 UPS Events 35
Device Connected This section is to set the usage power and connection status of other devices which connects to the same UPS as NetAgent uses. Fig
2.2.5 Email This page is to set Email details for use by NetAgent. Email SettingEmail Server This section is to set NetAgent Email Server . Note t
Fig.28 Email 38
2.2.6 SMS When UPS events occurs, it allows Short Message Signals (“SMS”) to be sent and received using a GSM/GPRS/CDMA Modem. Operation information
2.2.7 Modem (For 3 Ports NetAgent II only) This section is to configure Modem’s setting if 3 ports NetAgent connects with GSM/GPRS Modem. Modem Settin
2.2.8 WEB/Telnet This page is to set up the User Account in NetAgent. User Account User Name This section is to set a user name for NetAgent web p
2.2.9 System Time This page is to set NetAgent system time. You can provide NetAgent with up to 2 time servers or you can set a time zone. System Ti
2.2.9 NetFeeler II (For 3 Ports NetAgent II only) This page is to set Environmental sensors-NetFeeler II’s configurations. NetFeeler II Critical Und
2.6 AC power status _______________________________________ 60 2.7 Battery Status _________________________________________ 60 2.8 Status History ____
2.2.10 Language This page is to set the language interface for NetAgent. Interface Language This section is to set the language for NetAgent web
2.3 Log Information Sub-Menu : 2.3.1 Event Log 2.3.2 SMS 2.3.3 Data Log 2.3.4 Save Data Log NetAgent Log Record Model Log Information Single Port(D
Fig.35 Event Log 46
2.3.2 SMS This page is a SMS Event log. It shows a record of all mobile number, giving the Date/Time of the SMS sent and a detailed description of eac
2.3.3 Data Log This page is a UPS data log. It records UPS Input Voltage/Output Voltage/ Frequency/ Loading/Capacity/ Temperature. When reach to the l
Fig.37 Date Log 49
2.3.3 Save Data Log This function is to record RS232 UPS’s voltage, frequency, load, capacity, temperature..etc to save as another file for the other
2.4 Help Sub-Menu : 2.4.1 Search NetAgent 2.4.2 Serial Port Debug 2.4.3 Help 2.4.4 About 2.4.1 Search NetAgent This to display all the found NetA
2.4.3 Help This to help to illustrate the operation of NetAgent 2.4.4About About This to check Netagent’s Firmware/Hardware version and serial num
Firmware Update Setting Default FTP server is set as ftp.icv99.com with its username/password. Click on Update Now, NetAgent will connects to the FTP
Appendix B -3 Ports NetAgent II with SMS Modem ________________ 87 Appendix C –SMS Server with SMS Modme______________________ 91 4
Chapter 6. Telnet (Remote Configuration) Section1. Introduction NetAgent supports multiple Network Management systems and LAN protocols. After finishi
Fig.42 NetAgent Telnet window 1. Set IP Address. This function allows you to setup IP Address, Gateway Address, Subnet Mask parameters. 2. Set SNMP M
Chapter 7. ClientMate - Windows Shutdown Utility ClientMate is a utility for connecting to NetAgent. This utility is for the Windows platform. When t
2.1 Config When the ClientMate gets the signal from the NetAgent about the AC power failure or battery low signals, the ClientMate will based on the c
vi. Shutdown Windows To configure if shutdown or Sleep the Windows system when power failure. vii. When AC failed, commence computer shutdown sequenc
2.3 About Press this button could review the version information of the ClientMate, as here bellowed. Fig.47 ClientMate:About 2.4 Event log Press thi
2.5 IP address of connection Status ICON Description Already connect to NetAgent UPS at IP 211.21.67.51 Does not connect to any NetAgent. 2.6
Chapter 8. SNMPView – Windows Based UPS Management System Section1. Introduction SNMPView is a software to remotely monitor and control multiple
Section3. Install SNMPView n Put the NetAgent Utility CD into the CD driver. And execute the SNMPView program. o After installation, there will be a N
Section4. Using SNMPView When use SNMP view at the first time, the system will ask for input the user's name and password. Please enter the defau
Chapter1. Introduction Section1. Features NetAgent is a new generation SNMP (Simple Network Management Protocol) monitoring product. Not only coul
Section5. SNMPView Buttons When use SNMPView, configuration could be done by all function icons displayed or right click on the mouse to show function
Following is the main function icons and its reference chapter. Main List Sub List • 5.1.1 Enumerate • 5.1.2 Add Group • 5.1.3 Add UPS • 5.1.4 Dele
5.1 ENUMERATE(D) Start SNMPView and press the “Enumerate” button, SNMPView will start a search for all the NetAgent on network and list them in the m
5.1.4 DELETE UPS Highlight the unit to be deleted from main list and right click on it to choose Delete or use click on the Delete icon from main fu
5.1.7 Import Configuration This is to import the configuration of NetAgent UPS that saved 68
5.1.8 Open archive Event Log Open up “SnmpElog.dat”, SNMPView would show the event log of all NetAgent UPS: Open up “SnmpElog.dat”, event log would
5.1.9 Open archive Data Log Open up “SnmpDlog.dat”, SNMPView would show the event log of all NetAgent UPS: Open up “SnmpDlog.dat”, data log would sh
5.2 View(S) This is to choose the presentation format of NetAgent UPS. 5.2.1 Large Icons Large icon view to display IP address and its location. 5
5.2.3 Details Detailed Information displays NetAgent UPS’s IP address, name, input voltage, output voltage, battery capacity, load, frequency..etc. 5
5.3 Tools(P) Highlight NetAgent UPS device and configure. 5.3.1 Settings General This to configure UPS information, record UPS event, enable trap a
Section2. Applications 2.1 NetAgent makes your UPS on the Internet When the UPS connects with NetAgent, the system manager could check each and every
Trap List Double click on the trap that listed and configure UPS Loading To configure all the other devices and its load that connects with Ne
75
5.3.2 UPS Monitor Highlight NetAgent UPS device and configure. Or right click on the highlighted device and click on monitor device Meter Display Net
Event Log This display event happened with date/time and its description Control • Turn Off UPS: To shutdown UPS • Reboot UPS: UPS shuts down in 12
Once choose the function that to perform and click on “Execute” Note: UPS must supports those function to perform it Test Control • UPS Self Test: Ex
5.3.3 UPS Management To configure SNMP of its NetAgent UPS 79
5.4 System(S) To view event log, data log and configuration 5.4.1 Event Log Display event log , date/time and description of all NetAgent UPS 5.4.
5.4.3 SNMP Option To set NetAgent UPS’s parameter 81
5.5 User(U) Total of 8 users account can be created to manage and control its NetAgent UPS 5.5.1 Change Password To change existing user’s password t
5.6 Help(H) Display the current SNMPView version, and operation information 5.6.1 HTML Help This to check the operation of SNMPView 5.6.2 About Disp
Fig.1 NetAgent connection Software Fig.2 3 Port NetAgent II Diagram 3
Appendix A - Update the firmware of NetAgent UPS NetAgent provides the following convenient methods for user to update the latest firmware of the Net
2. Use FTP to update (suitable for BK,CK,DK,BP,CP,DP using firmware version 2.35 and later) The FTP is a easy and common way to upload the latest fir
3. Use IE browser to update (suitable for BK,CK,DK,BP,CP,DP version) This method is to enter the account, password and IP address of the NetAgent UPS
Appendix B -3 Ports NetAgent II with SMS Modem BP506 & SMS MODEM Hardware Installation: 1: A:GSM MODEM。 B:GSM MODEM Adaptor 。 C:N
card has password, invalid password. If such conditions happens, please unplug&plug the power on Modem and it shall ready SIM again. If Led doesn
BP506 Modem Configuration: 1、BP506 Modem 2.Modem communication Type→Select SMS 3.SMS Communication→Select GPRS
BP506 SMSConfiguration: BP506→Configuration→1.SMS 2.Select Local Modem 3.Enter BP506’s username and password
Appendix C –SMS Server with SMS Modme GPRS MODEM Installation: 1. Insert Sim card 2、 Connect DC adaptor to GPRS modem as well serial cable p
2:Once installed, the icon would appear on the tool bar 3:Right click on the SMS server icon and check modem status
3、NetAgent sends SMS via modem: 1. Click on SMS in the NetAgent Webpage 2. Enter the SMS server’s IP Service Port:NetAgent & SMS Server po